No. The SDM-CD8S was designed to switch dc loads (12 Vdc nominal; 1 A maximum per channel, total current on all channels not to exceed 6 A). The SDM-CD8S switches the - outputs, rather than the + output. This is called a low-side switch. The + output is the same voltage as the PWR used to power the SDM-CD8S to ground.
To switch an ac load, consider using an SDM-CD16ACA.